The Lake Shore Electric Corporation Vacuum Breaker (VB) Medium Voltage Automatic Transfer Switch provides dependable, positive, transfer to an emergency power source in the event of normal power source failure. The switch returns the system to the normal power source in an orderly fashion when normal power is restored. In the event that the emergency source fails, the switch will automatically return to the normal source when it becomes available, bypassing all time delays.
Our VB Series switch is offered in fixed or draw out designs. Much like our low voltage transfer switches, we can offer flexibility in our designs such as : special bussing to close couple to bus duct; special bussing to close couple to existing switchgear; service entrance rating; separate cable pull sections; front accessibility; side accessibility; utility metering sections; additional sections for related controls and monitoring; incorporation of monitoring and special protective equipment.
Lake Shore Electric Corporation VB Medium Voltage Automatic Transfer Switches utilize two electrically and mechanically interlocked vacuum circuit breakers. Each breaker, whether fixed or draw out utilizes a two-step stored energy mechanism. The breaker features a 3-Cycle (50ms) interrupting time, with mechanical endurance up to 20,000 operations. Try to find a load break switch that can accomplish that feat!
The transfer switches are available in current ranges from 600A, 1200A, 2000A, and 2500A with Short Circuit kA rms ratings up to 40. They are equipped with spring charging motor, manual charging handle, manual mechanical close/open pushbuttons, open/closed mechanical position indicators, stored energy operators, and spring charged/discharged indicators.
Not currently available.
Medium Voltage Operating & Maintenance Manual with MP7600 and Cutler Hammer VCP-T Vacuum Breakers
Medium Voltage Operating & Maintenance Manual with MP7600 and Square D VR Vacuum Breakers
*Medium Voltage Operating & Maintenance Manual with MP7650 and Cutler Hammer VCP-T Vacuum Breakers
*Medium Voltage Operating & Maintenance Manual with MP7650 and Square D VR Vacuum Breakers
*INSTALLED ON ALL MICROPROCESSOR CONTROLLED TRANSFER SWITCHES WITH SERIAL NUMBER HIGHER THAN 121-0000
Not currently available.